Home > Product > Smart Tank Farm > Water Quality Monitoring Products >  Inductive conductivity sensor


LOADING IMAGES

Inductive conductivity sensor

Low power consumptionLow maintenance costAnti interference design
Based on the conductivity of electrodeless inductive measurement, a generator is used to generate an alternating magnetic field in the primary coil, and an induced current is generated in the medium. The strength of the induced current depends on the conductivity, that is, the ion concentration in the medium. The induced current generates another magnetic field in the secondary coil. The receiver measures the induced current on the coil, thereby determining the conductivity of the medium. At the same time, the built-in temperature sensor can automatically compensate the temperature, which is suitable for online long-term monitoring environment.
Sample Now

Product Features

Categories of models
The specific modelsNetworkReferred to as"Terminal type (interface)Size
KRCFB-L



Features:
1. Digital sensor, direct output OF RS-485 digital signal, MODBUS/RTU support
2. Built-in temperature sensor, automatic temperature compensation
3. No electrode, so no polarization reaction
4. Complete electrical isolation of measurement and medium, high precision measurement of heavy and easy to precipitate medium or solution, low maintenance cost
5. Low power consumption of sensor, anti-interference design of internal circuit
Application scope:
Marine, industrial wastewater, pharmaceutical, biotechnology, industrial manufacturing and other online monitoring of the whole process.

Technical Parameter

The measured parameters
ProjectWithin the capacity
The output signalSupport RS-485,MODBUS/RTU protocol
Method of measurementNon-contact electromagnetic principle
Range0-200 mS/cm; The range is customized within 600mS/cm
PrecisionPlus or minus 1.5% F.S.
The resolution of the0.1 mS/cm


The power supply
ProjectWithin the capacity
The power supply12 or 24VDC±10%, 10mA;


Physical properties
ProjectWithin the capacity
SizeDiameter of 30 mm; Length of 185.5 mm;
Protection gradeIP68; Water depth 20 meters; Other custom
The service life of theSensor 3 years or above
The length of the cable5 meters (default), customizable
Sensor housing materialPVC; PEEK; Can be customized


Other parameters
ProjectWithin the   let
The working conditions0 ~ 65 ℃; < 0.6 Mpa; High temperature conductivity customization
Calibration modeTwo calibration
The response time10 seconds T90
Temperature compensationAutomatic temperature compensation (PT1000)


Product Size

Product Size drawing (unit: mm)


sc.png

Selection Guide

Product model




Spectrum26GHz























The theory of bandwidth
























Transmission power




Reception sensitivity1s



Application Scheme

Download Center